Mains analyser | |
Measurement circuit: | Single Phase with standard mains connector |
Current rating: | 16A rms continuous or national connector rating if lower |
Voltage ranges: | 115V (±200V pk) 230V (±400V pk) |
Current ranges: | ±24mA pk to ±400A pk in fifteen 2:1 ranges |
Frequency range: | 43 to 67Hz |
Shunt resistance: | 3mΩ |
Sampling rate: | 300 points per cycle |
Basic accuracy: | Better than 0.2% ±1mA, up to 16A |
Measured parameters: | Vrms, Vpk, Arms, Apk, Crest factors, THD, W, VA, power factor, frequency, inrush current |
Display modes: | Tabular display of all parameters including latest and highest inrush current. |
Monitor outputs: | Re-constructed Voltage and Current Signals |
Voltage ranges: | 115V (±200V pk) 230V (±400V pk) |
Current ranges: | ±24mA pk to ±400A pk in fifteen 2:1 ranges |
Frequency range: | 43 to 67Hz |
Shunt resistance: | 3mΩ |
Transforms window: | Continuous 4, 10, 12 or 16 cycle discrete fourier transforms |
Basic accuracy: | Better than 5% of limit or 0.2% of selected range whichever is the greater) ±1mA |
Voltage fluctuations and flicker meter | |
Measurements: | Voltage fluctuations dmax, dc, d(t) and flicker Pst and Plt to EN61000-3-3 and EN61000-4-5 |
Current rating: | 16A rms continuous, or national connector rating if lower |
Voltage ranges: | 115V (±200V pk) 230V (±400V pk) |
Fluctuation range: | 25% max. (relative to nominal voltage) |
General | |
Display: | 320 x 240 pixel backlit LCD |
Clock: | Realtime clock for time/date stamping of report data |
Interfaces: | Parallel printer, RS-232, USB |
Instrument supply: | 230V or 115V ±14%, 48Hz to 65Hz |
Operating range: | +5°C to 40°C, 20 to 80% RH |
Storage range: | -10°C to +60°C |
Dimensions: | 357(W) x 132(H) x 235(D)mm |
Weight: | 4.4kg |
Safety: | Complies with EN61010-1 |
EMC Compliance: | Complies with EN61326-1 |