| Input | | | | | Rated voltage | 220-230-240V AC | | | | Minimum input range | 140V from 70 to 80% of load/160V from 80% to 100% of load | | | | Maximum input range | 300V | | | | Rated frequency | 50/60Hz ±5Hz | | | | Rated current | 3.5A | | | | Power factor | > 0.97 | | | | By Pass | | | | | Voltage tolerance static | ±1.5% | | | | Frequency tolerance | ±0,5% | | | | Batteries | | | | | Type | VRLA AGM Maintenance-free lead-acid | | | | Recharge time | 4 hours | | | | OUTPUT | | | | | Rated voltage | 220 or 230 or 240V AC selectable ±1,5% | | | | Waveform | Sine wave | | | | Voltage distortion | | | | | Frequency | 50 or 60Hz selectable | | | | Frequency tolerance | ±0,5 % | | | | Crest factor | (Ipeak/Irms) 3 : 1 (up to 100% of load) | | | | Output sockets | 4 IEC 320 10A 4 IEC 320 10A | | | | Environmental | | | | | Weight | DLPR 100 16kg | | | | DLPR 100 21kg | | | | DLPR 100 30kg | | | | AC/AC | Efficiency 90% | | | | Communication | RS232 + communication interface slot | | | | Operating temperature | O°C to +40 °C, ideal for battery 15°C to +25°C | | | | Relative humidity | Protection Overload | Short-circuit - overvoltage - undervoltage - temperature - low battery | | | Safety compliance | EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC | EN 62040-3 | | | Surge capability | 3KA 8/20 µs | | | | Colour | Dark grey | | | | Noise | | | | |
|
|
|
|